Data Value
Input voltage +30 V Replacement device: < 8 mA
Existing device: £ 9 mA
Maximum cable length:
-> Shielded 1000 m
-> Unshielded 600 m
Protection against reversed voltage Yes
Overvoltage protection Up to 30 V DC
*) Input delay of the S500 module DC532. The transmission rate via serial buses has not been
taken into account.
For further information, please refer to the existing documentation
System description Advant Controller 31.
1.5.1.8.3 Technical Data of the Digital Outputs
Data Value
Connections X5/3.0, X5/3.1, X5/3.2, X5/3.3, X5/3.4, X5/3.5,
X5/3.6, X5/3.7
Type of digital outputs High-side switch
Demagnetization with inductive load With a varistor inside the device (with other
circuitry)
Switching frequency with ohmic load On request
Output voltage at signal 1 X4 / L+ (typ. 24 V) -0.8 V
Output delay: 0 -> 1 or 1 -> 0 On request
Maximum cable length:
-> Shielded 1000 m
-> Unshielded 600 m
For further information, please refer to the existing documentation
System description Advant Controller 31.
1.5.1.8.4 Technical data of the configurable inputs/outputs
Data Value
Connections X6/4.0, X6/4.1, X6/4.2, X6/4.3, X6/4.4, X6/4.5,
X6/4.6, X6/4.7
Use as digital input
See
Ä
Chapter 1.5.1.8.2 “Technical Data of
the Digital Inputs” on page 69
Use as digital output
See
Ä
Chapter 1.5.1.8.3 “Technical Data of
the Digital Outputs” on page 70
Replacement devices: I/O modules > Replacement device 07DC91-AD
2018/09/243ADR010122, 8, en_US70