EasyManua.ls Logo

ABB AC31 - Technical Data of the complete device

ABB AC31
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data of the complete device
Table 97: Supply voltage Vs
Data Value
Process voltage: Fuse for Vs+ 10 A, fast acting
Current consumption:
-> via Vs+ Replacement device: 0.15 A
Existing device DC501-CS31: approx. 60 ... 230 mA
- Inrush current via Vs+ (when
voltage is switched on)
0.06 A²s
Power consumption 5 W
For further information, please refer to the existing documentation
System description Advant Controller 31.
CAUTION!
System damage caused by voltage!
Exceeding the maximum supply or process voltage (>30 V DC) results in per-
manent system damage (destruction).
Table 98: Supply voltage V
Data Value
Process voltage:
-> Fuse for V+ 10 A, fast acting
-> Additional V-/Vs- connections
(GND)
X4 / -0, X4 / -1, X4 / -2, X4 / -3, X4 / -4, X4 / -5, X4 / -6,
X4 / -7, X4 / -8
Current consumption:
-> via V+ Replacement device: 0.15 A incl. load current
Existing device DC501-CS31: approx. 100 mA without
load current
- Inrush current via V+ (when
voltage is switched on)
0.013 A
2
s
Power consumption 220 W
Power consumption outputs
unloaded
6 W
Sensor supply voltage connections X4 / +0, X4 / +1, X4 / +2, X4 / +3, X4 / +4, X4 / +5, X4 /
+6, X4 / +7, X4 / +8
Current sensor supply voltage (all
connections combined)
Replacement device: max. 200 mA
Existing device DC501-CS31: Microfuse 8 A, fast acting
*)
*) The existing device contained an 8 A fuse to be exchanged by the user. The replacement
device has an integrated electronic current limiter instead.
AC31 Adapters
Replacement devices: I/O modules > Replacement unit DC501-CS31-AD
2018/09/24 3ADR010122, 8, en_US 153