Fig. 82: DIP switch for 07AC91-AD2
Please observe the following:
The function of the address DIP switch 8 (channel No. £ 7 or channel No. > 7) is no longer
supported. This DIP switch must be switched off. The outputs on connector X7 cannot be
configured as current outputs.
Unused voltage inputs must be configured as current inputs (due to wire-break detection
AX522 S500 module).
The operating mode (address DIP switch 1) must be set to "12 bit".
The DIP switches are read by the device only once after the supply voltage has been con-
nected.
For further information, please refer to the existing documentation
System description Advant Controller 31.
1.5.5.2.4 Measuring ranges of the analog channels
For the replacement device 07AC91-AD2, only the operating mode "12 bit" is relevant.
AC31 Adapters
Replacement devices: I/O modules > Replacement device 07AC91-AD2
2018/09/24 3ADR010122, 8, en_US 129