1.5.6.2.2 Electrical connection
Fig. 87: Electrical connection
Table 81: Pin assignment CS31 bus (X1)
Connector / Terminal Pin Assignment / Signal
X1 / Shield 1 Shield (internally connected to pin 2 and 6. No internal
connection to functional earth)
X1 / Shield 2 Shield (internally connected to pin 1 and 6. No internal
connection to functional earth)
X1 / B2 3 BUS 2
X1 / B1 4 BUS 1
X1 / NC 5 Not connected
X1 / Shield 6 Shield (internally connected to pin 1 and 2. No internal
connection to functional earth)
Correction to existing documentation
In the existing documentation, connection X1 / 2 is incorrectly documented as
"free / not connected". On the replacement device DC501-CS31-AD, the selec-
tion of the pin assignment of connector X1 is identical to the realization of
device DC501-CS31. Thus, the pin assignment described in this document is
valid for the replacement device and the existing device.