ABB AC31 - Analog outputs

ABB AC31
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data Value
Resolution in bits:
-> Ranges ±10 V, 0 ... 10 V 12 bit plus sign
-> Ranges 0 ... 20 mA, 4 ... 20 mA 12 bit without sign
-> Range Pt100, Pt1000, Ni1000: 0.1 °C
Resolution in mV, μA:
-> Range ±10 V approx. 2.5 mV
-> Range 0 ... 10 V approx. 2.5 mV
-> Range 0 ... 20 mA approx. 5 μA
-> Range 4 ... 20 mA approx. 4 μA
Relationship between input signal and hex
code
-100 % ... 0 ... +100 % = 9400H ... 0000H ...
6C00H (-27648 ... 0 ... 27648 decimal)
Conversion error of the analog values due to
non-linearity.
Adjustment error on delivery and resolution in
the nominal range
Typ. 0.5 %, max. 1 %
Use as digital input:
-> Signal 0 -30 V ... +5 V
-> Undefined signal state +5 V ... +13 V
-> Signal 1 +13 V ... +30 V
Max. cable length
2-core shielded and conductor cross section >
0.14 mm²
100 m
CAUTION!
Risk of overloading the analog input!
If an analog current sensor supplies a current in excess of 25 mA for more than
1 second during initialization, this input is switched off by the module (input pro-
tection).
Use only sensors with fast initialization or sensors without current peaks higher
than 25 mA. If this is not possible, protect the input by connecting a 10-volt
zener diode in parallel to I+ and I-.
For further information, please refer to the existing documentation
System description Advant Controller 31.
Analog outputs
Data Value
Number of channels per device 4
Connections Connector X10 (terminals 3.5, 3.6, 7.5 and
7.6)
Reference potential AGND2 (terminals 3.5, 3.6, 7.5 and 7.6)
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
2018/09/243ADR010122, 8, en_US50