Connection of the supply voltage
Fig. 19: Connection of the supply voltage
Table 12: Connector (X6)
Connector / Terminal Pin Assignment / Signal
X6 / L+ 40 Supply voltage +24 V DC
X6 / L+ 41 Supply voltage +24 V DC
X6 / M 42 Earth connection (0 V)
X6 / M 43 Earth connection (0 V)
X6 / functional earth 44 The functional earth (FE) is
connected to the Faston ter-
minal inside the device.
Ensure that no earth loops are
created and that FE and
Faston are connected to the
same earthing potential.
In addition to connecting the supply voltage (L+/M) to X6, the supply voltage (UP/ZP) must
be connected to all connectors.
ZP must be connected to all connectors (X1, X2, X3, X7, X8, X9).
UP must be connected to all connectors (X7, X8, X9).
L+/M and UP/ZP must always be supplied with voltage.
Connection for CS31 bus
Table 13: Connector (X5)
Connector / Terminal Pin Assignment / Signal
X5 / shield 37 Shield (functional earth)
X5 / B2 38 BUS2
X5 / B1 39 BUS1
Terminal "Shield" is internally connected to FE. The previous earthing meas-
ures, e.g. with clip at the switchgear cabinet, are still required.
Ä
Chapter 1.3
“System data and CS31 bus system data” on page 4
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD