Technical Data of the analog inputs
Data Value
Connections X2 / 2.0, X2 / 2.1, X2 / 2.2, X2 / 2.3, X3 / 2.4,
X3 / 2.5, X3 / 2.6, X3 / 2.7
Reference connections (AGND) X2 / 1.0, X2 / 1.1, X2 / 1.2, X2 / 1.3, X3 / 1.4,
X3 / 1.5, X3 / 1.6, X3 / 1.7
Type of inputs Voltage bipolar, current unipolar
Time constant of the input filter Voltage
Replacement device: 100 µs
Existing device: 470 µs
Conversion cycle *) Replacement device: 2 ms (over 8 inputs + 8
outputs)
Existing device: 8 ms
Resolution: range ± 10 V Replacement device: 2.4 mV, 12 bit + sign
Existing device: 5 mV, 11 bit + sign
Protection against reversed voltage Yes
Overvoltage protection Up to 30 V DC
*) Conversion cycle of S500 module AX522. The transmission via serial buses is slower.
Unused voltage inputs must be configured as current inputs (due to wire-break
detection AX522 S500 module).
For further information, please refer to the existing documentation
System description Advant Controller 31.
Technical Data of the analog outputs
Data Value
Connections X6 / 4.0, X6 / 4.1, X6 / 4.2, X6 / 4.3, X7 / 4.4,
X7 / 4.5, X7 / 4.6, X7 / 4.7
Reference connections (AGND) X6 / 3.0, X6 / 3.1, X6 / 3.2, X6 / 3.3, X7 / 3.4,
X7 / 3.5, X7 / 3.6, X7 / 3.7
Type of outputs Voltage bipolar, current unipolar
Configurability Replacement device: 4 current outputs avail-
able
Existing device: 8 current outputs available
Output load capability, as voltage output Replacement device: ± 10 mA
Existing device: +20 mA, -10 mA
Short-circuit-proof Yes
External supply protection Up to 30 V DC
Replacement devices: I/O modules > Replacement device 07AC91-AD2