Connector / Terminal Pin Assignment / Signal
X5 / 3.5 33 DC532 / C21
X5 / 3.6 34 DC532 / C22
X5 / 3.7 35 DC532 / C23
Table 31: Pin assignment 24 V DC 200 W (X4)
Connector / Terminal Pin Assignment / Signal
X4 / L+ 22 L+
X4 / L+ 23 L+
X4 / M 24 M
X4 / M 25 M
X4 / FE 26 FE
The device 07DC91-AD has 16 digital outputs, each with 0.5 A output current.
This results in a maximum output current of 8 A. With an output current of 4 A
and higher, both terminals (L+) of connector X4 must be used.
CAUTION!
System damage caused by voltage!
The exchange of a replacement device under voltage can cause permanent
system damage (destruction).
Fig. 40: Connection example: digital input
Replacement devices: I/O modules > Replacement device 07DC91-AD
2018/09/243ADR010122, 8, en_US62