EasyManua.ls Logo

ABB ACQ80-04 - Page 110

ABB ACQ80-04
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
110 Parameters
Fault/Event 2
Warning/Warning 3
Event/Event 4
No indication/No
indication
5
31.23 Wiring or earth fault Selects how the drive reacts to incorrect input power and
motor cable connection (ie. input power cable is connected to
drive motor connection).
Fault
No action No action taken. 0
Fault The drive trips on fault 3181 Wiring or earth fault.1
No. Name/Value Description Def/FbEq16
Inputs Indication
IN1 IN2 Running Stopped
00
Fault 5091 Safe torque
off
Event B5A0 Safe
torque off
01
Faults 5091 Safe
torque off and FA81
Safe torque off 1 loss
Event B5A0 Safe
torque off and fault
FA81 Safe torque off 1
loss
10
Faults 5091 Safe
torque off and FA82
Safe torque off 2 loss
Event B5A0 Safe
torque off and fault
FA82 Safe torque off 2
loss
1 1 (Normal operation)
Inputs
Indication (running or stopped)
IN1 IN2
0 0 Warning A5A0 Safe torque off
01
Warning A5A0 Safe torque off and fault FA81
Safe torque off 1 loss
10
Warning A5A0 Safe torque off and fault FA82
Safe torque off 2 loss
1 1 (Normal operation)
Inputs
Indication (running or stopped)
IN1 IN2
0 0 Event B5A0 STO event
01
Event B5A0 STO event and fault FA81 Safe
torque off 1 loss
10
Event B5A0 STO event and fault FA82 Safe
torque off 2 loss
1 1 (Normal operation)
Inputs
Indication (running or stopped)
IN1 IN2
0 0 None
0 1 Fault FA81 Safe torque off 1 loss
1 0 Fault FA82 Safe torque off 2 loss
1 1 (Normal operation)
ACQ80 FW.book Page 110 Thursday, February 14, 2019 11:33 AM