Parameters 127
36
36 Load analyzer
Peak value and amplitude logger settings.
See also section Load analyzer (page 49).
36.01 PVL signal source Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter 36.02 PVL filter time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters 36.10 … 36.15.
The peak value logger can be reset using parameter 36.09
Reset loggers. The date and time of the last reset are stored
into parameters 36.16 and 36.17 respectively.
Output power
Not selected None (peak value logger disabled). 0
Motor speed used 01.01 Motor speed used.1
Output frequency 01.06 Output frequency.3
Motor current 01.07 Motor current.4
Motor torque 01.10 Motor torque.6
DC voltage 01.11 DC voltage.7
Output power 01.14 Output power. 8
Speed ref ramp in 23.01 Speed ref ramp input.10
Speed ref ramp out 23.02 Speed ref ramp output.11
Speed ref used 24.01 Used speed reference.12
Torque ref used Not applicable
Freq ref used 28.02 Frequency ref ramp output.14
Process PID out 40.01 Process PID output actual.16
Other Source selection (see Terms and abbreviations). -
36.02 PVL filter time Peak value logger filtering time. See parameter 36.01 PVL
signal source.
2.00 s
0.00…120.00 s Peak value logger filtering time. 100 = 1 s
36.06 AL2 signal source Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters 36.40 … 36.49.
Each parameter represents an amplitude range, and shows
what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 36.07 AL2 signal scaling.
Amplitude logger 2 can be reset using parameter 36.09 Reset
loggers. The date and time of the last reset are stored into
parameters 36.50 and 36.51 respectively.
For the selections, see parameter 36.01 PVL signal source.
Motor torque
See parameter 36.01 for the selections.
36.07 AL2 signal scaling Defines the monitored signal value for the amplitude logger
AL2 that corresponds to 100% sample value.
100.00
0.00…32767.00 Signal value corresponding to 100%. 1 = 1
36.09 Reset loggers Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Done Reset completed or not requested (normal operation). 0
All Reset both the peak value logger and amplitude logger 2. 1
PVL Reset the peak value logger. 2
No. Name/Value Description Def/FbEq16