142 Parameters
46.22 At frequency
hysteresis
Defines the “at setpoint” limits for frequency control of the
drive. When the absolute difference between frequency
reference and actual frequency (01.06 Output frequency) is
smaller than 46.22 At frequency hysteresis, the drive is
considered to be “at setpoint”. This is indicated by bit 8 of
06.11 Main status word.
2.00 Hz
0.00…1000.00 Hz Limit for “at setpoint” indication in frequency control. 10 = 1
46.31 Above speed limit Defines the trigger level for “above limit” indication in speed
control. When actual speed exceeds the limit, bit 10 of 06.17
Drive status word 2 is set.
1500.00 rpm
0.00…30000.00
rpm
“Above limit” indication trigger level for speed control. 1 = 1
46.32 Above frequency
limit
Defines the trigger level for “above limit” indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of 06.17 Drive status word 2 is set.
50.00 Hz
0.00…1000.00 Hz “Above limit” indication trigger level for frequency control. 10 = 1
46.41 kWh pulse scaling Defines the trigger level for the “kWh pulse” on for 50 ms. The
output of the pulse is bit 9 of 05.22 Diagnostic word 3.
1.000 kWh
0.001…
1000.000 kWh
“kWh pulse” on trigger level. 1 = 1 kWh
46.43 Power decimals Defines the number of decimal places of power-related
parameters.
2
0...3 Number of decimal places of power parameters. 1 = 1
46.44 Current decimals Defines the number of decimal places of current-related
parameters.
1
0...3 Number of decimal places of current parameters. 1 = 1
49
49 Panel port
communication
Communication settings for the control panel port on the
drive.
49.01 Node ID number Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note: For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
1
1…32 Node ID. 1 = 1
49.03 Baud rate Defines the transfer rate of the link. 115.2 kbps
38.4 kbps 38.4 kbit/s. 1
57.6 kbps 57.6 kbit/s. 2
86.4 kbps 86.4 kbit/s. 3
No. Name/Value Description Def/FbEq16
01.06 (Hz)
0 Hz
Frequency reference + 46.22
Frequency reference (Hz)
Frequency reference - 46.22
Drive at setpoint
(06.11 bit 8 = 1)
ACQ80 FW.book Page 142 Thursday, February 14, 2019 11:33 AM