Parameters 67
Parameter listing
No. Name/Value Description Def/FbEq16
01
01 Actual values
Basic signals for monitoring the drive.
All parameters in this group are read-only unless otherwise
noted.
Note: Values of these actual signals are filtered with the filter
time defined in group 46 Monitoring/scaling settings. The
selection lists for parameters in other groups mean the raw
value of the actual signal instead. For example, if a selection
is “Output frequency it does not point to the value of
parameter 01.06 Output frequency but to the raw value.
01.01 Motor speed used Shows estimated motor speed.
A filter time constant for this signal can be defined by
parameter 46.11 Filter time motor speed.
-
-30000.00…
30000.00 rpm
Estimated motor speed. 1 = 1 rpm
01.02 Motor speed
estimated
Shows estimated motor speed in rpm.
A filter time constant for this signal can be defined by
parameter 46.11 Filter time motor speed.
-
-30000.00…
30000.00 rpm
Estimated motor speed. 1 = 1 rpm
01.03 Motor speed % Shows motor speed in percent of the synchronous motor
speed.
-
-1000.00…
1000.00%
Motor speed. 10 = 1%
01.06 Output frequency Shows estimated drive output frequency in Hz.
A filter time constant for this signal can be defined by
parameter 46.12 Filter time output frequency.
-
-500.00…500.00
Hz
Estimated output frequency. 10 = 1 Hz
01.07 Motor current Shows measured (absolute) motor current in A. -
0.00…30000.00 A Motor current. 1 = 1 A
01.08 Motor current % of
motor nom
Shows motor current (drive output current) in percent of the
nominal motor current.
-
0.0…1000.0% Motor current. 1 = 1%
01.09 Motor current % of
drive nom
Shows motor current (drive output current) in percent of the
nominal drive current.
-
0.0…1000.0% Motor current. 1 = 1%
01.10 Motor torque Shows motor torque in percent of the nominal motor torque.
See also parameter 01.30 Nominal torque scale.
A filter time constant for this signal can be defined by
parameter 46.13 Filter time motor torque.
-
-1600.0…1600.0% Motor torque. 10 = 1%
01.11 DC voltage Shows measured DC link voltage. -
0.00…2000.00 V DC link voltage. 10 = 1 V
01.13 Output voltage Shows calculated motor voltage in V AC. -
0…2000 V Motor voltage. 1 = 1 V
ACQ80 FW.book Page 67 Thursday, February 14, 2019 11:33 AM