Fieldbus control through the embedded fieldbus interface (EFB) 239
References
References for the ABB Drives profile and DCU Profile
The references are provided by MPPT and does not depend on any user settings.
Actual values
Actual values for the ABB Drives profile and DCU Profile
The ABB Drives profile supports the use of two fieldbus actual values, ACT1 and
ACT2. The actual values are 16-bit words each containing a sign bit and a 15-bit
integer. A negative value is formed by calculating the two’s complement from the
corresponding positive value.
The actual values are scaled as defined by parameters 99.08
, 99.09, 46.03 and
46.04; which scaling is in use depends on the setting of parameters 58.28 EFB act1
type and 58.29 EFB act2 type (see page 152).
99.09 (with motor nominal speed)
99.08 (with motor nominal frequency)
0
-20000
20000
DriveFieldbus
0
10000
-10000
46.03 (with torque reference)
46.04 (with power reference)
-(99.09) (with motor nominal speed)
-(99.08) (with motor nominal frequency)
-(46.03) (with torque reference)
-(46.04) (with power reference)
ACQ80 FW.book Page 239 Thursday, February 14, 2019 11:33 AM