EasyManua.ls Logo

ABB ACQ80-04 - Standard AO

ABB ACQ80-04
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88 Parameters
12.101 AI1 percent value Value of analog input AI1 in percent of AI1 scaling (12.18 AI1
max - 12.17 AI1 min).
100.00
0.00…100.00% AI1 value 100 = 1%
12.102 AI2 percent value Value of analog input AI2 in percent of AI2 scaling (12.28 AI2
max - 12.27 AI2 min).
0.00
0.00…100.00% AI2 value 100 = 1%
13
13 Standard AO
Configuration of standard analog outputs.
13.02 AO force selection The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters 13.02 and 13.11).
0b0000
0b0000…0b1111 Forced values selector for analog o utputs AO1 and AO2. 1 = 1
13.11 AO1 actual value Shows value of AO1 in mA
This parameter is read-only.
-
0.000…22.000 mA Value of AO1. 1 = 1 mA
13.12 AO1 source Selects a signal to be connected to analog output AO1. Output
frequency
Zero None. 0
Motor speed used 01.01 Motor speed used (page 67). 1
Output frequency 01.06 Output frequency (page 67). 3
Motor current 01.07 Motor current (page 67). 4
Motor current % of
motor nominal
01.08 Motor current % of motor nom (page 67). 5
Motor torque 01.10 Motor torque (page 67). 6
DC voltage 01.11 DC voltage (page 67). 7
Output power 01.14 Output power (page 68). 8
Speed ref used 12
Freq ref used 28.02 Frequency ref ramp output (page 101). 14
Process PID out 40.01 Process PID output actual (page 130). 16
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter 35.11 Temperature 1
source. See also section Motor thermal protection (page 44).
20
Temp sensor 2
excitation
The output is used to feed an excitation current to the
temperature sensor 2, see parameter 35.21 Temperature 2
source. See also section Motor thermal protection (page 44).
21
Abs motor speed
used
01.61 Abs motor speed used (page 70). 26
Abs motor speed % 01.62 Abs motor speed % (page 70). 27
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force AO1 to value of parameter 13.13 AO1 forced value. (0 = Normal mode)
1 1 = Force AO2 to value of parameter 13.23 AO2 forced value. (0 = Normal mode)
2…15 Reserved
ACQ80 FW.book Page 88 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Related product manuals