122 Parameters
1 × Pt100 analog
I/O
Pt100 sensor connected to a standard analog input selected
by parameter 35.14 Temperature 1 AI source and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group 12 Standard AI to V (volt).
• In parameter group 13 Standard AO, set the source
selection parameter of the analog output to Temp sensor 1
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
5
2 × Pt100 analog
I/O
As selection 1 × Pt100 analog I/O, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
6
3 × Pt100 analog
I/O
As selection 1 × Pt100 analog I/O, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
7
Direct temperature The temperature is taken from the source selected by
parameter 35.14 Temperature 1 AI source. The value of the
source is assumed to be degrees Celsius.
11
35.12 Temperature 1 fault
limit
Defines the fault limit for temperature supervision function 1.
When measured temperature 1 exceeds the limit, the drive
trips on fault 4981 External temperature 1.
The unit is selected by parameter 96.16 Unit selection.
130 °C or
266 °F
-60…5000 °C or
-76…9032 °F
Fault limit for temperature monitoring function 1. 1 = 1 unit
35.13 Temperature 1
warning limit
Defines the warning limit for temperature supervision
function 1. When measured temperature 1 exceeds the limit,
warning A491 External temperature 1 is generated.
The unit is selected by parameter 96.16 Unit selection.
110 ° C or
230 °F
-60…5000 °C or
-76…9032 °F
Warning limit for temperature monitoring function 1. 1 = 1 unit
35.14 Temperature 1 AI
source
Specifies the analog input when the setting of 35.11
Temperature 1 source requires measurement through an
analog input.
Not selected
Not selected None. 0
AI1 actual value Analog input AI1 on the control unit. 1
AI2 actual value Analog input AI2 on the control unit. 2
Other Source selection (see Terms and abbreviations on page 64). -
35.21 Temperature 2
source
Selects the source from which measured temperature 2 is
read.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
Disabled
Disabled None. Temperature monitoring function 2 is disabled. 0
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 122 Thursday, February 14, 2019 11:33 AM