48 Program features
Local control loss detection (parameter 49.05)
The parameter selects how the drive reacts to a control panel or PC tool
communication break.
AI supervision (parameters 12.0312.04)
The parameters select how the drive reacts when an analog input signal moves out of
the minimum and/or maximum limits specified for the input. This can be due to broken
I/O wiring or sensor.
Fan control (95.200)
Fan control prevents overheating and dust accumulation in the drive. The user can
set the fan to run continuously in maximum speed (Always ON [1]) or can set to run
the fan in a controlled mode (Auto[0]), as per the load speed.
Automatic fault resets
The drive can automatically reset itself after over-current, over-voltage, undervoltage
and external faults. The user can also specify a fault that is automatically reset.
By default, automatic resets are off and must be specifically activated by the user.
WARNING! Before you activate the function, make sure that no dangerous
situations can occur.
The function resets the drive automatically and continues operation after a fault.
Settings
Parameters 31.1231.16 (page 108).