32 Program features
Control interfaces
Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V) or current (0/4…20 mA) with parameters
in firmwares ISPDA,ISPD2 and ISPD4. Each input can be filtered, inverted and
scaled.
Settings
Parameter group 12 Standard AI (page 84).
Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Analog output 1 can be
set as a voltage (0/2…10 V) or current (0/4…20 mA) output with parameters in
firmwares ISPDA,ISPD2 and ISPD4. Analog output 2 always uses current. Each
output can be filtered, inverted and scaled.
Settings
Parameter group 13 Standard AO (page 88).
Programmable digital inputs and outputs
The control unit has six digital inputs.
Digital input DI5 can be used as high frequency input. The panel shows the
appropriate selection only.
Settings
Parameter groups 10 Standard DI, RO (page 78) and 11 Standard DIO, FI, FO (page
82).
Programmable frequency input and output
Digital input DI5 can be configured as high frequency input. The panel shows the
appropriate selection only.
Settings
Parameter groups 10 Standard DI, RO (page 78) and 11 Standard DIO, FI, FO (page
82).
Programmable relay outputs
The control unit has three relay outputs. The signal to be indicated by the outputs can
be selected by parameters.