Fieldbus control through the embedded fieldbus interface (EFB) 243
Coils (0xxxx reference set)
Coils are 1-bit read/write values. Control Word bits are exposed with this data type.
The table below summarizes the Modbus coils (0xxxx reference set). Note that the
references are 1-based index which match the address transmitted on the wire.
Reference ABB Drives profile DCU Profile
000001 OFF1_CONTROL STOP
000002 OFF2_CONTROL START
000003 OFF3_CONTROL Reserved
000004 INHIBIT_OPERATION Reserved
000005 RAMP_OUT_ZERO RESET
000006 RAMP_HOLD EXT2
000007 RAMP_IN_ZERO RUN_DISABLE
000008 RESET STOPMODE_RAMP
000009 JOGGING_1 STOPMODE_EMERGENCY_RAMP
000010 JOGGING_2 STOPMODE_COAST
000011 REMOTE_CMD Reserved
000012 EXT_CTRL_LOC RAMP_OUT_ZERO
000013 USER_0 RAMP_HOLD
000014 USER_1 RAMP_IN_ZERO
000015 USER_2 Reserved
000016 USER_3 Reserved
000017 Reserved FB_LOCAL_CTL
000018 Reserved FB_LOCAL_REF
000019 Reserved Reserved
000020 Reserved Reserved
000021 Reserved Reserved
000022 Reserved Reserved
000023 Reserved USER_0
000024 Reserved USER_1
000025 Reserved USER_2
000026 Reserved USER_3
000027 Reserved Reserved
000028 Reserved Reserved
000029 Reserved Reserved
000030 Reserved Reserved
000031 Reserved Reserved
000032 Reserved Reserved
ACQ80 FW.book Page 243 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ80-04 and is the answer not in the manual?

ABB ACQ80-04 Specifications

General IconGeneral
BrandABB
ModelACQ80-04
CategoryDC Drives
LanguageEnglish

Related product manuals