78 Parameters
0.00.0.0...255.255.
255.255
-1=1
07.06 Loading package
name
Name of the firmware loading package. -
07.07 Loading package
version
Version number of the firmware loading package. 0.00.0.0
0.00.0.0...255.255.
255.255
-1=1
07.11 Cpu usage Microprocessor load in percent. 0
0…100% Microprocessor load. 1 = 1
10
10 Standard DI, RO
Configuration of digital inputs and relay outputs.
10.02 DI delayed status Shows the status of digital inputs DI1…DI6. Bits 0…5 reflect
the delayed status of DI1…DI6.
Example: 0000000000010011b = DI5, DI2 and DI1 are on,
DI3, DI4 and DI6 are off.
This word is updated only after a 2 ms activation/deactivation
delay. When the value of a digital input changes, it must
remain the same in two consecutive samples, that is for 2 ms,
for the new value to be accepted.
This parameter is read-only.
0b0000
0b0000...0b1111 Delayed sta tus for digital inputs. 1 = 1
10.03 DI force selection The electrical statuses of the digital inputs can be overridden
for eg. testing purposes. A bit in parameter 10.04 DI forced
data is provided for each digital input, and its value is applied
whenever the corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters 10.03 and 10.04).
0b0000
0b0000...0b1111 Override selec tion for digital inp uts. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 DI1 1 = Digital input 1 is ON.
1 DI2 1 = Digital input 2 is ON.
2 DI3 1 = Digital input 3 is ON.
3 DI4 1 = Digital input 4 is ON.
4 DI5 1 = Digital input 5 is ON.
5 DI6 1 = Digital input 6 is ON.
6…15 Reserved
Bit Value
0 1 = Force DI1 to value of bit 0 of parameter 10.04 DI forced data. (0 = Normal mode)
1 1 = Force DI2 to value of bit 1 of parameter 10.04 DI forced data. (0 = Normal mode)
2 1 = Force DI3 to value of bit 2 of parameter 10.04 DI forced data. (0 = Normal mode)
3 1 = Force DI4 to value of bit 3 of parameter 10.04 DI forced data. (0 = Normal mode)
4 1 = Force DI5 to value of bit 4 of parameter 10.04 DI forced data. (0 = Normal mode)
5 1 = Force DI6 to value of bit 5 of parameter 10.04 DI forced data. (0 = Normal mode)
6…15 Reserved