184 Additional parameter data
04.12 2nd latest fault Data 0x0000...0xffff - 1 = 1
04.13 3rd latest fault Data 0x0000...0xffff - 1 = 1
04.16 Latest warning Data 0x0000...0xffff - 1 = 1
04.17 2nd latest warning Data 0x0000...0xffff - 1 = 1
04.18 3rd latest warning Data 0x0000...0xffff - 1 = 1
05 Diagnostics
05.01 On-time counter Real 0…65535 d 1 = 1
05.02 Run-time counter Real 0…65535 d 1 = 1
05.03 Pump run hours Real 0.0...429496729.5 h1 = 1
05.04 Fan on-time counter Real 0…65535 d 1 = 1
05.10 Control board temperature Real -100…300 °C 10 = 1
05.11 Inverter temperature Real -40.0…160.0 % 10 = 1
05.20 Diagnostic word 1 PB 0b0000...0b1111 - 0 b0000
05.21 Diagnostic word 2 PB 0b0000...0b1111 - 0 b0000
05.22 Diagnostic word 3 PB 0b0000...0b1111 - -
05.80 Motor speed at fault Real -30000.00…30000.00 rpm 100 = 1 rpm
05.81 Output frequency at fault Real -500.00…500.00 Hz 100 = 1 Hz
05.82 DC voltage at fault Real 0.00…2000.00 V 100 = 1 V
05.83 Motor current at fault Real 0.00…30000.00 A 100 = 1 A
05.84 Motor torque at fault Real -1600.0…1600.0 % 10 = 1%
05.85 Main status word at fault PB 0000h…FFFFh - 1 = 1
05.86 DI delayed status at fault PB 0b0000...0b1111 - 1 = 1
05.87 Inverter temperature at fault PB -40.0…160.0 °C 10 = 1°C
05.88 Reference used at fault Real -500.00...500.00 Hz/
-1600.0…1600.0%/
30000.00...30000.00 rpm
Hz/
%/
rpm
100 = 1 Hz/
10 = 1%/
100 = 1 rpm
06 Control and status words
06.01 Main control word PB 0x0000...0xffff - 1 = 1
06.11 Main status word PB 0x0000...0xffff - 1 = 1
06.16 Drive status word 1 PB 0b0000...0b1111 - 1 = 1
06.17 Drive status word 2 PB 0b0000...0b1111 - 1 = 1
06.18 Start inhibit status word PB 0b0000...0b1111 - 1 = 1
06.19 Speed control status word PB 0b0000...0b1111 - 1 = 1
06.29 MSW bit 10 selection Binary src 0...2 - 1 = 1
06.30 MSW bit 11 selection Binary src 0...2 - 1 = 1
06.31 MSW bit 12 selection Binary src 0...2 - 1 = 1
06.32 MSW bit 13 selection Binary src 0...1 - 1 = 1
06.33 MSW bit 14 selection Binary src 0...1 - 1 = 1
07 System info
07.03 Drive rating id List --1 = 1
07.04 Firmware name List --1 = 1
07.05 Firmware version Data 0.00.0.0...255.255.255.255 - 1 = 1
07.06 Loading package name List --1 = 1
07.07 Loading package version Data 0.00.0.0...255.255.255.255 - 1 = 1
07.11 Cpu usage Real 0…100 % 1 = 1%
No. Name Type Range Unit FbEq32