74 Parameters
05.86 DI delayed status at
fault
Displays the DI delayed status (10.02) at which fault
occurred. For the bit list, see parameter 10.02 DI delayed
status.
0b0000
0b0000...0b1111 DI del ayed s tatus at fa ult. 1 = 1
05.87 Inverter
temperature at fault
Displays the inverter temperature (05.11) at which fault
occurred.
-
-40…160°C Inverter temperature at fault. 1 = 1°C
05.88 Reference used at
fault
Displays the reference used (28.01/23.01) at which fault
occurred. The type of the reference depends on the selected
operation mode (79.10).
-
06
06 Control and status
words
Drive control and status words.
06.01 Main control word The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such
as digital inputs, the fieldbus interfaces and the application
program).
For the bit descriptions see page 253. The related status
word and state diagram are presented on pages 255 and 256
respectively.
This parameter is read-only.
0x0000
0x0000...0xffff Main control word. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name
0 Off1 control
1 Off2 control
2 Off3 control
3 Run
4 Ramp out zero
5 Ramp hold
6 Ramp in zero
7 Reset
8 Inching 1
9 Inching 2
10 Remote cmd
11 Ext ctrl loc
12 User bit 0
13 User bit 1
14 User bit 2
15 User bit 3