254 Fieldbus control through a fieldbus adapter
5 Ramp hold 1 ramp function.
Proceed to RAMP FUNCTION GENERATOR: ACCELERATOR D.
0 Halt ramping (Ramp Function Generator output held).
6 Ramp in zero 1 Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus interface is set as the
source for this signal by drive parameters.
0 Force Ramp function generator input to zero.
7 Reset 0=>1 Fault reset if an active fault exists. Proceed to SWITCH-ON
INHIBITED.
Note: This bit is effective only if the fieldbus interface is set as the
source of the reset signal by drive parameters.
0 Continue normal operation.
8 Inching 1 1 Accelerate to inching (jogging) setpoint 1.
Notes:
• Bits 4…6 must be 0.
• See also section Parameter 97.01 Switching frequency reference
and 97.02 Minimum switching frequency (page 162). (page 44).
0 Inching (jogging) 1 disabled.
8 Reserved
9 Inching 2 1 Accelerate to inching (jogging) setpoint 2.
See notes at bit 8.
0 Inching (jogging) 2 disabled.
9 Reserved
10 Remote cmd 1 Fieldbus control d.
0 Control word and reference not getting through to the drive, except
for bits 0…2.
11 Ext ctrl loc 1 Select External Control Location EXT2. Effective if control location is
parameterized to be selected from fieldbus.
0 Select External Control Location EXT1. Effective if control location is
parameterized to be selected from fieldbus.
12 User bit 0 1 User configurable
0
13 User bit 1 1
0
14 User bit 2 1
0
15 User bit 3 1
0
Bit Name Value STATE/Description