Program features 53
Settings
Parameters 96.02 (page 165) and 96.100…96.102 (page 169).
Sine filter support
The control program has a setting that enables the use of ABB sine filters (available
separately). With a sine filter connected to the output of the drive, bit 1 of 95.15
Special HW settings must be switched on. The setting forces the drive to use scalar
motor control mode. It also limits switching and output frequencies to prevent the
drive from operating at filter resonance frequencies, and to protect the filter from
overheating.
Contact your local ABB representative before connecting a sine filter from another
manufacturer.
Settings
Parameter 95.15 Special HW settings (page 163).
ACQ80 FW.book Page 53 Thursday, February 14, 2019 11:33 AM