160 Parameters
80.21 Pump nominal
speed
Defines the nominal speed of pump. This value is used
for flow calculation (80.01).
0
0...30000 rpm Speed. 1 = 1
80.26 Calc low speed Defines the minimum speed/frequency limit below which flow
is not calculated.
5.00
0.00...32767.00
Hz
Minimum speed/frequency limit for flow calculation.
1 = 1
80.29 Reset flow Resets the measured flow data of actual signals to
zero in the parameters 80.06 Today’s flow and 80.03 To tal
flow.
Not selected
Not selected Disables the flow reset. 0
Reset Activates the flow reset. 1
80.50 PQ curve P1 Defines the power input of pump at point 1 on the PQ
performance curve.
See section Flow calculation (page35).
0.00
0.00...32767.00 kW Power input of pump at point 1.
80.51 PQ curve P2 Defines the power input of pump at point 2 on the PQ
performance curve.
See parameter 80.50 PQ curve P2.
0.00
80.52 PQ curve P3 Defines the power input of pump at point 3 on the PQ
performance curve.
See parameter 80.50 PQ curve P2.
0.00
80.53 PQ curve P4 Defines the power input of pump at point 4 on the PQ
performance curve.
See parameter 80.50 PQ curve P2.
0.00
80.54 PQ curve P5 Defines the power input of pump at point 5 on the PQ
performance curve.
See parameter 80.50 PQ curve P2.
0.00
80.60 Q value Q1 Defines the flow rate at point 1 on the PQ performance curve.
See section Flow calculation (page35).
0.00
0.00...
200000.00 m
3
/h
Flow rate at point 1 of the PQ curve. 1 = 1
80.61 Q value Q2 Defines the flow rate at point 2 on the PQ performance curve.
See parameter 80.60 Q value Q1.
0.00
80.62 Q value Q3 Defines the flow rate at point 3 on the PQ performance curve.
See parameter 80.60 Q value Q1.
0.00
80.63 Q value Q4 Defines the flow rate at point 4 on the PQ performance curve.
See parameter 80.60 Q value Q1.
0.00
80.64 Q value Q5 Defines the flow rate at point 5 on the PQ performance curve.
See parameter 80.60 Q value Q1.
0.00
82
82 Pump protections
Settings for pup dry run protection.
See section Dry run protection (page 38).
82.02 Dry run source Selects the source for dry run protection.
Min load
current
Not selected 0 (always off). 0
Selected 1 (always on). 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 160 Thursday, February 14, 2019 11:33 AM