Parameters 161
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Min load current Enables the dry run protection when the actual load is below
the dry run current limit.
8
Other [bit] Source selection (see Terms and abbreviations on page 64). -
82.46 Dry run current limit Defines the dry run current limit. When the actual current
goes below the dry run current limit for a defined time (82.47),
the drive considers it as a dry run condition and trips on the
fault, D4B0 Running dry.
0.00
0.00...3000.00 Current limit. 100 = 1
82.47 Dry run trip monitor
time
Defines the time to monitor dry run current limit. After the
defined time elapses, the drive considers it as dry run
condition and trips on the fault, D4B0 Running dry.
120.0
1.0...300.0 Run trip monitor time. 10 = 1
82.48 Dry run reset time Defines the rest time to reset the dry run fault (D4B0). The
drive starts automatically if it receives a start command.
120.0
1.0...18000.0 Dry run reset time. 10 = 1
83
83 Pump cleaning
Settings for the pump cleaning sequence.
See section Pump cleaning (page 36).
83.01 Pump cleaning
status
Displays the status of pump cleaning. Disabled
Disabled Pump cleaning is disabled. 0
Clean pump Pump cleaning is active. 1
No triggers
configured
Pump cleaning is not active. 2
Waiting for
triggering
Waiting for triggering signal. 3
83.02 Pump cleaning
progress
Displays the pump cleaning progress. 0
0.0...100.0% Percentage 10 = 1
83.03 Total cleaning count Displays the cleaning count. Cleaning count increments by
one, when the sequence of cleaning cycles are completed.
For example, if 83.16 Cycles in cleaning program is set as 3,
the pump cleaning completes after three cycles of reverse
and forward motions of the pump and the cleaning count
changes to 1.
0
0...1000000 Total cleaning count. 1 = 1
83.12 Start pump cleaning Enables/disables the pump cleaning. Not active
Not active Pump cleaning is not active. 0
Start cleaning now Starts pump cleaning immediately. 1
DI4 Starts pump cleaning when DI4 goes high. 2
DI5 Starts pump cleaning when DI5 goes high. 3
DI6 Starts pump cleaning when DI6 goes high. 4
No. Name/Value Description Def/FbEq16