Additional parameter data 183
Parameter groups 1…9
No. Name Type Range Unit FbEq32
01 Actual values
01.01 Motor speed used Real -30000.00…30000.00 rpm 100 = 1 rpm
01.02 Motor speed estimated Real -30000.00…30000.00 rpm 100 = 1 rpm
01.03 Motor speed % Real -1000.00…1000.00 % 100 = 1%
01.06 Output frequency Real -500.00…500.00 Hz 100 = 1 Hz
01.07 Motor current Real 0.00…30000.00 A 100 = 1 A
01.08 Motor current % of motor nom Real 0.0…1000.0 % 10 = 1%
01.09 Motor current % of drive nom Real 0.0…1000.0 % 10 = 1%
01.10 Motor torque Real -1600.0…1600.0 % 10 = 1%
01.11 DC voltage Real 0.00…2000.00 V 100 = 1 V
01.13 Output voltage Real 0…2000 V 1 = 1 V
01.14 Output power Real -32768.00…32767.00 kW 100 = 1 unit
01.15 Output power % of motor nom Real -300.00…300.00 % 100 = 1%
01.16 Output power % of drive nom Real -300.00…300.00 % 100 = 1%
01.17 Motor shaft power Real -32768.00…32767.00 kW or hp 100 = 1 unit
01.18 Inverter GWh counter Real 0…65535 GWh 1 = 1 GWh
01.19 Inverter MWh counter Real 0…1000 MWh 1 = 1 MWh
01.20 Inverter kWh counter Real 0…1000 kWh 1 = 1 kWh
01.24 Flux actual % Real 0…200 % 1 = 1%
01.30 Nominal torque scale Real 0.000…4000000 N·m 1000 = 1 unit
01.50 Current hour kWh Real 0.00…1000000.00 kWh 100 = 1 kWh
01.51 Previous hour kWh Real 0.00…1000000.00 kWh 100 = 1 kWh
01.52 Current day kWh Real 0.00…1000000.00 kWh 100 = 1 kWh
01.53 Previous day kWh Real 0.00…1000000.00 kWh 100 = 1 kWh
01.54 Cumulative inverter energy Real 0…1000000.00 kWh 100 = 1 kWh
01.55 Inverter GWh counter
(resettable)
Real -200000000.0…
200000000.0
kWh 1 = 1 kWh
01.56 Inverter MWh counter
(resettable)
Real
0…65535
GWh 1 = 1 kWh
01.57 Inverter kWh counter
(resettable)
Real
0…1000
MWh 1 = 1 kWh
01.58 Cumulative inverter energy
(resettable)
Real
0…1000
kWh 1 = 1 kWh
01.61 Abs motor speed used Real 0.00…30000.00 rpm 100 = 1 rpm
01.62 Abs motor speed % Real 0.00…1000.00% % 100 = 1%
01.63 Abs output frequency Real 0.00…500.00 Hz Hz 100 = 1 Hz
01.64 Abs motor torque Real 0.0…1600.0 % 10 = 1%
01.65 Abs output power Real 0.00…32767.00 kW 100 = 1 kW
01.66
Abs output power % motor nom
Real 0.00…300.00 % 100 = 1%
01.67 Abs output power % drive nom Real 0.00…300.00 % 100 = 1%
01.68 Abs motor shaft power Real 0.00…32767.00 kW or hp 100 = 1 kW
01.69 Load Speed Real 0.00...30000.00 rpm 100 = 1 rpm
03 Input references
03.01 Panel reference Real -10000.00…100000.00
-
100 =
1
03.02 Panel reference remote Real -10000.00…100000.00
-
100 =
1
03.05 FB A reference 1 Real -10000.00…100000.00 - 100 = 1
03.06 FB A reference 2 Real -10000.00…100000.00 - 100 = 1
03.09 EFB reference 1 Real -30000.00…30000.00 - 100 = 1
03.10 EFB reference 2 Real -30000.00…30000.00 - 100 = 1
04 Warnings and faults
04.01 Tripping fault Data 0x0000...0xffff - 1 = 1
04.02 Active fault 2 Data 0x0000...0xffff - 1 = 1
04.03 Active fault 3 Data 0x0000...0xffff - 1 = 1
04.06 Active warning 1 Data 0x0000...0xffff - 1 = 1
04.07 Active warning 2 Data 0x0000...0xffff - 1 = 1
04.08 Active warning 3 Data 0x0000...0xffff - 1 = 1
04.11 Latest fault Data 0x0000...0xffff - 1 = 1
ACQ80 FW.book Page 183 Thursday, February 14, 2019 11:33 AM