52 Program features
User parameter sets
The drive supports four user parameter sets that can be saved to the permanent
memory and recalled using drive parameters. It is also possible to use digital inputs to
switch between user parameter sets. To change a user parameter set, make sure the
drive is not modulating.
A user parameter set contains all editable values in parameter groups 10…99 except
the following:
• forced I/O values such as parameters 10.03 DI force selection and 10.04 DI
forced data
• I/O extension module settings (group 15)
• fieldbus communication settings (groups 50…53 and 58)
• parameter 95.01 Supply voltage.
As the motor settings are included in the user parameter sets, make sure the settings
correspond to the motor used in the application before recalling a user set. In an
application where different motors are used with the drive, perform the motor ID run
with each motor and the save the results in different user sets. The appropriate set
can then be recalled when the motor is switched on.
Settings
Parameters 96.10…96.13 (page 167).
User lock
For better cyber security, it is highly recommended that you set a master pass code to
prevent changing of parameter values and/or the loading of firmware and other files.
WARNING! ABB will not be liable for damages or losses caused by the failure
to activate the user lock using a new pass code. See Cybersecurity disclaimer
(page 15).
To activate the user lock for the first time, enter the default pass code, 10000000, into
96.02 Pass code. This will make parameters 96.100…96.102 visible. Then enter a
new pass code into 96.100 Change user pass code, and confirm the code in 96.101
Confirm user pass code. In 96.102 User lock functionality, define the actions that you
want to prevent (we recommend you select all the actions unless otherwise required
by the application).
To close the user lock, enter an invalid pass code into 96.02 Pass code, activate
96.08 Control board boot, or cycle the power. With the lock closed, parameters
96.100…96.102 are hidden.
To reopen the lock, enter your pass code into 96.02 Pass code. This will again make
parameters 96.102…96.102 visible.