Parameters 155
58.103 Data I/O 3 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400003.
For the selections, see parameter 58.101 Data I/O 1.
Ref2 16bit
58.104 Data I/O 4 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400004.
For the selections, see parameter 58.101 Data I/O 1.
SW 16bit
58.105 Data I/O 5 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400005.
For the selections, see parameter 58.101 Data I/O 1.
Act1 16bit
58.106 Data I/O 6 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400006.
For the selections, see parameter 58.101 Data I/O 1.
Act2 16bit
58.107 Data I/O 7 Parameter selector for Modbus register address 400007.
For the selections, see parameter 58.101 Data I/O 1.
None
…… … …
58.114 Data I/O 14 Parameter selector for Modbus register address 400014.
For the selections, see parameter 58.101 Data I/O 1.
None
79
79 Start stop control
Start/stop enable signal source selection; positive/negative
reference enable signal source selection. See also chapter
Start-Stop control (page 33).
79.01 Solar status word1 Solar status word 1.
This parameter is read-only.
0b0000
0b0000...0b1111 Sol ar stat us word 1. 1 = 1
79.02 Solar status word2 Solar status word 2.
This parameter is read-only.
0b0000
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Ready ON 1 = Ready to switch on.
1 Ready run 1 = Operation enabled.
2 Running 1 = Drive is modulating.
3 Fault 1 = Drive in fault state.
4 Dry run 1 = Dry run detected.
5 DC over volt 1 = Excessive intermediate circuit DC voltage detected.
6 DC under volt 1 = Insufficient intermediate circuit DC voltage.
7 Minimum speed 1 = Minimum speed alarm active.
8 Short circuit 1 = Short circuit in motor cables or motor, or internal fault in the drive
9 Earth fault earth (ground) fault in motor or motor cable.
10 Motor phase loss 1 = Motor phase missing. 0 = No motor circuit fault.
11 Supply phase loss 1 = Intermediate circuit DC voltage is oscillating due to missing input
power line phase or blown fuse.
12 Motor stall 1 = Motor is operating in stall region due to excessive load
or insufficient motor power.
13 Over current 1 = Output current exceeds trips level.
14 Ext fault1 1= External fault 1.
15 Start delay active 1 = Start delay alarm active.