68 Parameters
01.14 Output power Shows drive output power. A filter time constant for this
signal can be defined by parameter 46.14 Filter time power.
-
-32768.00
32767.00 kW
Output power. 1 = 1 unit
01.15 Output power % of
motor nom
Shows output power in percent of the nominal motor power. -
-300.00… 300.00% Output power. 1 = 1%
01.16 Output power % of
drive nom
Shows output power in percent of the nominal drive power. -
-300.00… 300.00% Output power. 1 = 1%
01.17 Motor shaft power Shows estimated mechanical power at motor shaft. The unit
is selected by parameter 96.16 Unit selection.
-
-32768.00
32767.00 kW or hp
Motor shaft power. 1 = 1 unit
01.18 Inverter GWh
counter
Shows amount of energy that has passed through the drive
(in either direction) in full gigawatt-hours. The minimum value
is zero.
-
0…65535 GWh Energy in GWh. 1 = 1 GWh
01.19 Inverter MWh
counter
Shows amount of energy that has passed through the drive
(in either direction) in full megawatt-hours. Whenever the
counter rolls over, 01.18 Inverter GWh counter is
incremented. The minimum value is zero.
-
0…1000 MWh Energy in MWh. 1 = 1 MWh
01.20 Inverter kWh
counter
Shows amount of energy that has passed through the drive
(in either direction) in full kilowatt-hours. Whenever the
counter rolls over, 01.19 Inverter MWh counter is
incremented. The minimum value is zero.
-
0…1000 kWh Energy in kWh. 10 = 1 kWh
01.24 Flux actual % Shows used flux reference in percent of nominal flux of motor. -
0…200% Flux reference. 1 = 1%
01.30 Nominal torque
scale
Shows torque that corresponds to 100% of nominal motor
torque. The unit is selected by parameter 96.16 Unit
selection.
Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is calculated
from other motor data.
-
0.000…4000000
N·m or lb·ft
Nominal torque. 1 = 100 unit
01.50 Current hour kWh Shows current hour energy consumption. This is the energy
of the last 60 minutes (not necessarily continuous) the drive
has been running, not the energy of a calendar hour.
The value is set to the value before the power cycle when the
drive is again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh