Parameters 69
01.51 Previous hour kWh Shows previous hour energy consumption.
The value 01.50 Current hour kWh is stored here when its
values has been cumulated for 60 minutes. The value is set
to the value before the power cycle when the drive is again up
and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.52 Current day kWh Shows current day energy consumption. This is the energy of
the last 24 hours (not necessarily continuous) the drive has
been running, not the energy of a calendar day.
The value is set to the value before the power cycle when the
drive is again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.53 Previous day kWh Shows previous day energy consumption.
The value 01.52 Current day kWh is stored here when its
value has been cumulated for 24 hours. The value is set to
the value before the power cycle when the drive is again up
and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.54 Cumulative inverter
energy
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. The minimum value is zero.
-
-200000000.0…
200000000.0 kWh
Energy in kWh. 10 = 1 kWh
01.55 Inverter GWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.55…01.58 resets all of them.
-
0…65535 GWh Energy in GWh. 1 = 1 GWh
01.56 Inverter MWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over, 01.55 Inverter MWh counter (resettable) is incremented.
The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.55…01.58 resets all of them.
-
0…1000 MWh Energy in MWh. 1 = 1 MWh
01.57 Inverter kWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over, 01.56 Inverter kWh counter (resettable) is incremented.
The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.55…01.58 resets all of them.
-
0…1000 kWh Energy in kWh. 10 = 1 kWh
01.58 Cumulative inverter
energy (resettable)
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.55…01.58 resets all of them.
-
-200000000.0…
200000000.0 kWh
Energy in kWh. 10 = 1 kWh
No. Name/Value Description Def/FbEq16