Additional parameter data 191
40.62 PID internal setpoint actual Real -200000.00...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.79 Set 1 units List 0...31 Depends
on
selection
-
40.89 Set 1 setpoint multiplier Real -200000.00...200000.00 --
40.90 Set 1 feedback multiplier Real -200000.00...200000.00 - 100 = 1
40.91 Feedback data storage Real -327.68…327.67 - 100 = 1
40.92 Setpoint data storage Real -327.68…327.67 - 100 = 1
40.96 Process PID output% Real -100.00...100.00 % -
40.97 Process PID feedback% Real -100.00...100.00 % -
40.98 Process PID setpoint% Real -100.00...100.00 % -
40.99 Process PID deviation% Real -100.00...100.00 % -
46 Monitoring/scaling settings
46.01 Speed scaling Real 0.00…30000.00 rpm 100 = 1 rpm
46.02 Frequency scaling Real 0.10…1000.00 Hz 100 = 1 Hz
46.03 Torque scaling Real 0.1…1000.0 % 10 = 1%
46.04 Power scaling Real 0.10…30000.00 kW or
0.10…40200.00 hp
kW or hp 10 = 1 unit
46.05 Current scaling Real 0…30000 A 1 = 1 A
46.06 Speed ref zero scaling Real 0.00 … 30000.00 rpm 100 = 1 rpm
46.07 Frequency ref zero scaling Real 0.00 … 1000.00 Hz 100 = 1 Hz
46.11 Filter time motor speed Real 2…20000 ms 1 = 1 ms
46.12 Filter time output frequency Real 2…20000 ms 1 = 1 ms
46.13 Filter time motor torque Real 2…20000 ms 1 = 1 ms
46.14 Filter time power Real 2…20000 ms 1 = 1 ms
46.21 At speed hysteresis Real 0.00…30000.00 rpm 100 = 1 rpm
46.22 At frequency hysteresis Real 0.00…1000.00 Hz 100 = 1 Hz
46.31 Above speed limit Real 0.00…30000.00 rpm 100 = 1 rpm
46.32 Above frequency limit Real 0.00…1000.00 Hz 100 = 1 Hz
46.41 kWh pulse scaling Real 0.001…1000.000 kWh 1000 = 1 kWh
46.43 Power decimals Real 0...3 - 1 = 1
46.44 Current decimals Real 0...3 - 1 = 1
49 Panel port communication
49.01 Node ID number Real 1…32 - 1 = 1
49.03 Baud rate List 1…5 - 1 = 1
49.04 Communication loss time Real 0.3…3000.0 s 10 = 1 s
49.05 Communication loss action List 0…3 - 1 = 1
49.06 Refresh settings List 0…1 - 1 = 1
50 Fieldbus adapter (FBA)
50.01 FBA A enable List 0…1 - 1 = 1
50.02 FBA A comm loss func List 0…5 - 1 = 1
50.03 FBA A comm loss t out Real 0.3…6553.5 s 10 = 1 s
50.04 FBA A ref1 type List 0...2, 4, 5 - 1 = 1
50.05 FBA A ref2 type List Not applicable
50.06 FBA A SW sel List 0…1 - 1 = 1
50.07 FBA A actual 1 type List --1 = 1
50.08 FBA A actual 2 type List Not applicable
50.09 FBA A SW transparent source Analog
src
--1 = 1
50.10 FBA A act1 transparent source Analog
src
--1 = 1
50.11 FBA A act2 transparent source Analog
src
Not applicable
50.12 FBA A debug mode List 0…1 - 1 = 1
50.13 FBA A control word Data 0.0.0.0.0...FF.FF.FF.FF - 1 = 1
50.14 FBA A reference 1 Real -2147483648…
2147483647
-1 = 1
No. Name Type Range Unit FbEq32
ACQ80 FW.book Page 191 Thursday, February 14, 2019 11:33 AM