190 Additional parameter data
40 Process PID set 1
40.01 Process PID output actual Real -200000.00...200000.00 % 100 = 1 PID
customer unit
40.02 Process PID feedback actual Real -200000.00...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.03 Process PID setpoint actual Real -200000.00...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.04 Process PID deviation actual Real -200000.00...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.06 Process PID status word PB 0b0000…0b1111 - 1 = 1
40.07 Process PID operation mode List 0…2 - 1 = 1
40.08 Set 1 feedback 1 source Analog
src
--1 = 1
40.11 Set 1 feedback filter time Real 0.000…30.000 s 1000 = 1 s
40.14 Set 1 setpoint scaling Real -200000.00...200000.00 --
40.15 Set 1 output scaling Real -200000.00...200000.00 --
40.16 Set 1 setpoint 1 source Analog
src
--1 = 1
40.24 Set 1 internal setpoint 0 Real -200000.00...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.26 Set 1 setpoint min Real -200000.00...200000.00 - 100 = 1
40.27 Set 1 setpoint max Real -200000.00...200000.00 - 100 = 1
40.28 Set 1 setpoint increase time Real 0.0…1800.0 s 10 = 1 s
40.29 Set 1 setpoint decrease time Real 0.0…1800.0 s 10 = 1 s
40.30 Set 1 setpoint freeze enable Binary src --1 = 1
40.31 Set 1 deviation inversion Binary src 0...1 - 1 = 1
40.32 Set 1 gain Real 0.01…100.00 - 100 = 1
40.33 Set 1 integration time Real 0.0…9999.0 s 10 = 1 s
40.34 Set 1 derivation time Real 0.000…10.000 s 1000 = 1 s
40.35 Set 1 derivation filter time Real 0.0…10.0 s 10 = 1 s
40.36 Set 1 output min Real -100.00...100.00 - 10 = 1
40.37 Set 1 output max
Real -100.00...100.00 - 10 = 1
40.38 Set 1 output freeze enable Binary src --1 = 1
40.39 Set 1 deadband range Real 0.0...200000.00 - 100 = 1
40.40 Set 1 deadband delay Real 0.0...3600.0 s 10 = 1 s
40.43 Set 1 sleep level Real 0.0...200000.00 - 10 = 1
40.44 Set 1 sleep delay Real 0.0…3600.0 s 10 = 1 s
40.45 Set 1 sleep boost time Real 0.0…3600.0 s 10 = 1 s
40.46 Set 1 sleep boost step Real 0.0...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.47 Set 1 wake-up deviation Real -200000.00...200000.00 PID
customer
units
100 = 1 PID
customer unit
40.48 Set 1 wake-up delay Real 0.00…60.00 s 100 = 1 s
40.49 Set 1 tracking mode Binary src --1 = 1
40.50 Set 1 tracking ref selection Analog
src
0...4 - 1 = 1
40.58 Set 1 increase prevention Binary src 0...1 - 1 = 1
40.59 Set 1 decrease prevention Binary src 0...1 - 1 = 1
40.60 Set 1 PID activation source List --1 = 1
40.61 Setpoint scaling actual Real -200000.00...200000.00 - 100 = 1
No. Name Type Range Unit FbEq32