Fault tracing 213
5696 PU state feedback State feedback from output
phases does not match control
signals.
Contact your local ABB representative.
5697 Charging feedback Charging feedback signal
missing.
Check the feedback signal coming from
the charging system
5698 Unknown PU fault The power unit logic generated
a fault which is not known by
software.
Check the logic and software
compatibility.
50A0 Fan Cooling fan stuck or
disconnected.
Check fan operation and connection.
Replace fan if faulty.
6181 FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6306 FBA A mapping file Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6481 Task overload Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6487 Stack overflow Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
64A1 Internal file load File read error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
64A3 Application loading Application file incompatible or
corrupted.
Check the auxiliary code. See actions for
each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
8007 The application contains the
wrong system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
8008 The application is empty. In Automation Builder, give a “Clean”
command and reload the application.
8009 The application contains
invalid tasks.
In Automation Builder, check application
task configuration, give a “Clean all”
command, and reload the application.
800A The application contains an
unknown target (system)
library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
64A4 Rating ID fault Rating ID load error. Contact ABB.
64A6 Adaptive program Fault in adaptive program. Check the fault code extension.
Code
(hex)
Fault / Aux. code (aux
code visible only on
assistant control panel
and drive composer)
Cause What to do
ACQ80 FW.book Page 213 Thursday, February 14, 2019 11:33 AM