Parameters 167
01.51 Previous hour kWh Previous hour energy consumption. The value 01.50 Current
hour kWh is stored here when its values has been cumulated
for 60 minutes. The value is set to the value before the power
cycle when the drive is again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.52 Current day kWh Current day energy consumption. This is the energy of the
last 24 hours (not necessarily continuous) the drive has been
running, not the energy of a calendar day. The value is set to
the value before the power cycle when the drive is again up
and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.53 Previous day kWh Previous day energy consumption. The value 01.52 Current
day kWh is stored here when its value has been cumulated
for 24 hours. The value is set to the value before the power
cycle when the drive is again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.54 Cumulative inverter
energy
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. The minimum value is zero.
-
-200000000.0…
200000000.0 kWh
Energy in kWh. 10 = 1 kWh
01.55 Inverter GWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.5501.58 resets all of them.
-
0…65535 GWh Energy in GWh. 1 = 1 GWh
01.56 Inverter MWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over, 01.55 Inverter GWh counter (resettable) is incremented.
The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.5501.58 resets all of them.
-
0....1000 MWh Energy in MWh. 1 = 1 MWh
01.57 Inverter MWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over, 01.56 Inverter MWh counter (resettable) is incremented.
The minimum value is zero.
You can reset the value by setting it to zero. Resetting any of
parameters 01.5501.58 resets all of them.
-
0…1000 kWh Energy in kWh. 10 = 1 kWH
01.58 Inverter kWh
counter (resettable)
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. The minimum value is zero.
Yo u c a n r e s e t t h e v a l u e b y s e t t i n g i t t o z e r o . R e s e t t i n g a n y o f
parameters 01.5501.58 resets all of them.
-
-200000000.0…
200000000.0 kWh
Energy in kWh. 10 = 1 kWH
01.61 Abs motor speed
used
Absolute value of parameter 01.01 Motor speed used.-
0.00… 30000.00
rpm
Estimated motor speed. See par.
46.01
No. Name/Value Description Def/FbEq16