Parameters 367
99.10 Motor nominal
power
Defines the nominal motor power. The setting must match the
value on the rating plate of the motor. If multiple motors are
connected to the drive, enter the total power of the motors.
The unit is selected by parameter 96.16 Unit selection.
Note: This parameter cannot be changed while the drive is
running.
0.75 kW
0.00… 10000.00
kW or hp
Nominal power of the motor. 1 = 1 unit
99.11 Motor nominal cos
Φ
Defines the cosphi of the motor for a more accurate motor
model. The value is not obligatory, but is useful with an
asynchronous motor, especially when performing a standstill
identification run.
Notes:
• Do not enter an estimated value. If you do not know the
exact value, leave the parameter at zero.
• This parameter cannot be changed while the drive is
running.
0.00
0.00…1.00 Cosphi of the motor. 100 = 1
99.12 Motor nominal
torque
Defines the nominal motor shaft torque for a more accurate
motor model. Not obligatory. The unit is selected by
parameter 96.16 Unit selection.
Note: This parameter cannot be changed while the drive is
running.
0.000
N·m or lb·ft
0.000…4000000.000
N·m or
0.000…2950248.597
lb·ft
Nominal motor torque. 1 = 100 unit
No. Name/Value Description Def/FbEq16