162 Parameters
23.28 Variable slope
enable
Activates the variable slope function, which controls the slope
of the speed ramp during a speed reference change. This
allows for a constantly variable ramp rate to be generated,
instead of just the standard two ramps normally available.
If the update interval of the signal from an external control
system and the variable slope rate (23.29 Variable slope rate)
are equal, the resulting speed reference (23.02 Speed ref
ramp output) is a straight line.
This function is only active in remote control.
Off
Off Variable slope disabled. 0
On Variable slope enabled (not available in local control). 1
Other [bit] Source selection (see Terms and abbreviations on page 92). -
23.29 Variable slope rate Defines the rate of the speed reference change when variable
slope is enabled by parameter 23.28 Variable slope enable.
For the best result, enter the reference update interval into
this parameter.
50 ms
2…30000 ms Variable slope rate. 1 = 1 ms
24
24 Speed reference
conditioning
Speed error calculation; speed error window control
configuration; speed error step.
See the control chain diagrams on pages 425 and 426.
24.01 Used speed
reference
Displays the ramped and corrected speed reference (before
speed error calculation). See the control chain diagram on
page 425.
This parameter is read-only.
-
-6000.00
6000.00 rpm
Speed reference used for speed error calculation. See par.
46.01
24.02 Used speed
feedback
Displays the speed feedback used for speed error calculation.
See the control chain diagram on page 425.
This parameter is read-only.
-
-6000.00
6000.00 rpm
Speed feedback used for speed error calculation. See par.
46.01