256 Parameters
Other Source selection (see Terms and abbreviations on page 92). -
……
53.12 FBA A data out12 See parameter 53.01 FBA A data out1. None
54
58 Embedded fieldbus
Configuration of the embedded fieldbus (EFB) interface.
See also chapter Fieldbus control through the embedded
fieldbus interface (EFB) (page 383).
58.01 Protocol enable Enables/disables the embedded fieldbus interface and selects
the protocol to use.
Notes:
When the embedded fieldbus interface is enabled, the
drive-to-drive link functionality is automatically disabled.
This parameter cannot be changed while the drive is
running.
None
None None (communication disabled). 0
Modbus RTU Embedded fieldbus interface is enabled and uses the Modbus
RTU protocol.
1
58.02 Protocol ID Displays the protocol ID and revision.
This parameter is read-only.
-
Protocol ID and revision. 1 = 1
58.03 Node address Defines the node address of the drive on the fieldbus link.
Values 1…247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter 58.06
Communication control.
1
0…255 Node address (values 1…247 are allowable). 1 = 1
58.04 Baud rate Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter 58.06
Communication control.
19.2 kbps
9.6 kbps 9.6 kbit/s. 2
19.2 kbps 19.2 kbit/s. 3
38.4 kbps 38.4 kbit/s. 4
57.6 kbps 57.6 kbit/s. 5
76.8 kbps 76.8 kbit/s. 6
115.2 kbps 115.2 kbit/s. 7
58.05 Parity Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter 58.06
Communication control.
8 EVEN 1
8 NONE 1 Eight data bits, no parity bit, one stop bit. 0
8 NONE 2 Eight data bits, no parity bit, two stop bits. 1
8 EVEN 1 Eight data bits, even parity bit, one stop bit. 2
8 ODD 1 Eight data bits, odd parity bit, one stop bit. 3
58.06 Communication
control
Validates any changes in the EFB settings, or activates silent
mode.
Enabled
Enabled Normal operation. 0