132 Parameters
13.28 AO2 source max Defines the real maximum value of the signal (selected by
parameter 13.22 AO2 source) that corresponds to the
maximum required AO2 output value (defined by parameter
13.30 AO2 out at AO2 src max). See parameter 13.27 AO2
source min.
100.0
-32768.0 …
32767.0
Real signal value corresponding to maximum AO2 output
value.
1 = 1
13.29 AO2 out at AO2 src
min
Defines the minimum output value for analog output AO2.
See also drawing at parameter 13.27 AO2 source min.
0.000 mA
0.000 … 22.000 mA Minimum AO2 output value. 1000 = 1 mA
13.30 AO2 out at AO2 src
max
Defines the maximum output value for analog output AO2.
See also drawing at parameter 13.27 AO2 source min.
20.000 mA
0.000 … 22.000 mA Maximum AO2 output value. 1000 = 1 mA
13.91 AO1 data storage Storage parameter for controlling analog output AO1 eg.
through fieldbus.
In 13.12 AO1 source, select AO1 data storage. Then set this
parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data (58.101…58.124)
to AO1 data storage.
0.00
-327.68 … 327.67 Storage parameter for AO1. 100 = 1
13.92 AO2 data storage Storage parameter for controlling analog output AO2 eg.
through fieldbus.
In 13.22 AO2 source, select AO2 data storage. Then set this
parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data (58.101…58.124)
to AO2 data storage.
0.00
-327.68 … 327.67 Storage parameter for AO2. 100 = 1
16
19 Operation mode
Selection of local and external control location sources and
operating modes.
See also section Operating modes of the drive (page 22).
19.01 Actual operation
mode
Displays the operating mode currently used.
See parameters 19.11…19.14.
This parameter is read-only.
-
Zero None. 1
Speed Speed control (in Vector motor control mode). 2
Torque Torque control (in Vector motor control mode). 3
Min The torque selector is comparing the output of the speed
controller (25.01 Torque reference speed control) and torque
reference (26.74 Torque ref ramp out) and the smaller of the
two is used.
4
Max The torque selector is comparing the output of the speed
controller (25.01 Torque reference speed control) and torque
reference (26.74 Torque ref ramp out) and the greater of the
two is used.
5
Add The speed controller output is added to the torque reference.6
Scalar (Hz) Frequency control in scalar motor control mode. 10
Scalar (rpm) Speed control in scalar motor control mode. 11
No. Name/Value Description Def/FbEq16