98 Parameters
01.68 Abs motor shaft
power
Absolute value of 01.17 Motor shaft power.-
0.00 … 32767.00
kW
Motor shaft power. 1 = 1 unit
01.70 Ambient
temperature %
Measured temperature of incoming cooling air.
The amplitude range of 0…100% corresponds to 0…60 °C
See also 01.31 Ambient temperature.
-
-200.00 … 200.00% Cooling air temperature. 1 = 1%
03
03 Input references
Values of references received from various sources.
All parameters in this group are read-only unless otherwise
noted.
03.01 Panel reference Local reference given from the control panel or PC tool. -
-100000.00 …
100000.00
Local control panel or PC tool reference. 1 = 10
03.02 Panel reference 2 Remote reference given from the control panel or PC tool. -
-30000.00 …
30000.00
Remote control panel or PC tool reference. 1 = 10
03.05 FB A reference 1 Reference 1 received through fieldbus adapter A.
See also chapter Fieldbus control through a fieldbus adapter
(page 407).
-
-100000.00 …
100000.00
Reference 1 from fieldbus adapter A. 1 = 10
03.06 FB A reference 2 Reference 2 received through fieldbus adapter A. -
-100000.00 …
100000.00
Reference 2 from fieldbus adapter A. 1 = 10
03.09 EFB reference 1 Scaled reference 1 received through the embedded fieldbus
interface. The scaling is defined by 58.26 EFB ref1 type.
1 = 10
-30000.00 …
30000.00
Reference 1 received through the embedded fieldbus
interface.
1 = 10
03.10 EFB reference 2 Scaled reference 2 received through the embedded fieldbus
interface. The scaling is defined by 58.27 EFB ref2 type.
1 = 10
-30000.00 …
30000.00
Reference 2 received through the embedded fieldbus
interface.
1 = 10
03.11 DDCS controller ref
1
Reference 1 received from the external (DDCS) controller.
The value has been scaled according to parameter 60.60
DDCS controller ref1 type.
See also section External controller interface (page 34).
1 = 10
-30000.00 …
30000.00
Scaled reference 1 received from external controller. 1 = 10
03.12 DDCS controller ref
2
Reference 2 received from the external (DDCS) controller.
The value has been scaled according to parameter 60.61
DDCS controller ref2 type.
1 = 10
-30000.00 …
30000.00
Scaled reference 2 received from external controller. 1 = 10