252 Parameters
50.13 FBA A control word Displays the raw (unmodified) control word sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h …
FFFFFFFFh
Control word sent by master to fieldbus adapter A. -
50.14 FBA A reference 1 Displays raw (unmodified) reference REF1 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
2147483647
Raw REF1 sent by master to fieldbus adapter A. -
50.15 FBA A reference 2 Displays raw (unmodified) reference REF2 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
2147483647
Raw REF2 sent by master to fieldbus adapter A. -
50.16 FBA A status word Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h …
FFFFFFFFh
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value
1
Displays raw (unmodified) actual value ACT1 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
50.18 FBA A actual value
2
Displays raw (unmodified) actual value ACT2 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
2147483647
Raw ACT2 sent by fieldbus adapter A to master. -