290 Parameters
95.13 Reduced run mode (Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required. A value
other than 0 activates the reduced run function.
If the control program cannot detect the number of modules
specified by this parameter, a fault (5695 Reduced run) is
generated.
See section Reduced run function (page 76).
0 = Reduced run disabled
1…12 = Number of modules available
Note: This parameter cannot be changed while the drive is
running.
0
0…65535 Number of inverter modules available -
95.14 Connected modules (Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules have
been detected by the control program.
-
0000h…FFFFh Inverter modules connected. 1 = 1
0000b…0111b Hardware options configuration word. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Module 1 1 = Module 1 has been detected.
1 Module 2 1 = Module 2 has been detected.
……
11 Module 12 1 = Module 12 has been detected.
12…15 Reserved