Electrical installation 139
Note: Connection between BINT board and BDFC board in the module is ready-made at
the factory.
Connecting a PC
Connection procedure
A PC (with eg, the Drive composer PC tool) can be connected to the supply / inverter unit
as follows:
1. Connect an ACS-AP-x control panel to the supply / inverter control unit either by using
an Ethernet (eg, CAT5E) networking cable, or by inserting the panel into the panel
holder (if present).
WARNING! Do not connect the PC directly to the control panel connector of the
supply / inverter unit as this can cause damage.
2. Remove the USB connector cover on the front of the control panel.
3. Connect an USB cable (Type A to Type Mini-B) between the USB connector on the
control panel (3a) and a free USB port on the PC (3b).
4. The panel will display an indication whenever the connection is active.
Note: It is also possible to connect the PC through an optional diagnostics and panel
interface (FDPI). The FDPI is used for branching the panel bus and chaining a control
panel or PC tool to several drives. See FDPI-xx user’s manual (3AUA0000113618
[English]).
5. See the documentation of the PC tool for setup instructions.