Ordering information 309
Main AC fuses
The AC fuses protect the input cables and the main contactor against short circuits. The
main AC fuses are used in such ACS880-04 configurations that there are a main switch-
disconnector and a main contactor, too. For the dimension drawings, see section Main AC
fuses on page 385.
Supply unit AC fuses
These fuses protect the supply module for short circuits. Supply unit AC fuses are used in
such ACS880-04 configurations that there is a main circuit breaker, or a main switch-
disconnector and a main contactor in case of two or more supply modules (6-pulse) or four
or more supply modules (12-pulse). For the dimension drawings, see section AC fuses on
page 382.
Main contactors
You can use the main contactors for the on-off control of the AC input power. The
contactors can make and break the full load current.
The contactor package includes:
• contactor unit
• fixing screws
• 2 × normally-open + 2 × normally-closed auxiliary contacts.
For the dimension drawings, see section Main contactor on page 378.
Varistor kit (UL/CSA)
See page 275.
ACS880-04-… Fuse (IEC) Qty Ordering code
Type Data
U
N
= 690 V (Range 525 … 690 V)
2300A-7+A004 170M7062 2000 A, 690 V 6 68689589
ACS880-04-…
Fuse (IEC) Qty Ordering code
Type Data
U
N
= 690 V (Range 525 … 690 V)
2300A-7+A004 170M6414 1000 A, 690 V 12 68333296
ACS880-04-…
Fuse (UL, CSA) Qty Ordering code
Type Data
U
N
= 690 V (Range 525 … 690 V)
2300A-7+A004 170M6414 1000 A, 690 V 12 68333296
ACS880-04-… Main contactor (IEC) Qty Ordering code
Type Information
U
N
= 690 V (Range 525 … 690 V)
2300A-7+A004 AF2050-30-22-70 2050 A (I
Th
), 1000 V (U
e
) 2 3AUA0000051805