Technical data 327
Losses, cooling data and noise
ACS880-04-… P
loss
Air flow Noise
kW
m
3
/h ft
3
/min
dB
U
N
= 400 V (Range 380 … 415 V)
1140A-3 18.0 4290 2525 73
1250A-3 21.0 5720 3367 74
1480A-3 25.0 5720 3367 74
1760A-3 29.0 5720 3367 74
2210A-3 37.0 8580 5050 76
2610A-3 44.0 8580 5050 76
0990A-3+A004 15.0 5720 3367 73
1250A-3+A004 21.0 5720 3367 74
1480A-3+A004 25.0 5720 3367 74
1760A-3+A004 29.0 5720 3367 74
2210A-3+A004 35.0 10010 5892 76
2610A-3+A004 44.0 10010 5892 76
U
N
= 500 V (Range 380 … 500 V)
1070A-5 18.0 4290 2525 73
1320A-5 22.0 5720 3367 74
1450A-5 25.0 5720 3367 74
1580A-5 27.0 5720 3367 74
1800A-5 32.0 7150 4208 75
1980A-5 36.0 7150 4208 75
0990A-5+A004 16.0 5720 3367 73
1320A-5+A004 22.0 5720 3367 74
1450A-5+A004 25.0 5720 3367 74
1580A-5+A004 27.0 5720 3367 74
1800A-5+A004 32.0 7150 4208 75
1980A-5+A004 36.0 7150 4208 75
U
N
= 690 V (Range 525…690 V)
0800A-7 16.0 4290 2525 73
0900A-7 20.0 4290 2525 74
1160A-7 26.0 5720 3367 74
1450A-7 32.0 7150 4208 75
1650A-7 36.5 7150 4208 75
2300A-7 52.0 10010 5892 76
0800A-7+A004 16.0 5720 3367 73
0950A-7+A004 20.0 5720 3367 74
1160A-7+A004 26.0 5720 3367 74
1450A-7+A004 32.0 7150 4208 75
1650A-7+A004 36.5 7150 4208 75
2300A-7+A004 52.0 11440 6733 77
3AXD00000601909
Definitions
P
loss
Heat dissipation. Total losses with nominal power
Noise Noise with fans running at nominal speed