Technical data 329
Tightening torques
For the tightening torques, see Cabinet design and construction instructions for ACS880
air-cooled and liquid-cooled multidrive modules (3AUA0000107668 [English]).
Electrical power network specification
Motor connection data
Supply voltage 400 V AC units; 380/400/415 V AC 3-phase ± 10%. This is indicated in type
designation label as typical input voltage levels (3~ 400 V AC).
500 V AC units; 440/460/480/500 V AC 3-phase ± 10%. This is indicated in type
designation label as typical input voltage levels (3~ 400/480/500 V AC).
690 V AC units; 525…690 V AC (525…600 V AC in corner-grounded TN
systems) 3-phase ± 10%. This is indicated in type designation label as typical
input voltage levels (3~ 525/600/690 V AC).
Network type TN (grounded) and IT (ungrounded) systems. 525…600 V AC in corner-
grounded TN systems
Frequency 50/60 Hz, Variation ± 5% of the nominal frequency
Imbalance Maximum 3% of nominal phase-to-phase voltage
Short-circuit withstand
strength
IEC/EN 61439-1:2009
Supply units with the ABB-defined main switch-disconnector and fuses:
Rated peak withstand current I
pk
= 105 kA
Rated short-time withstand current I
cw
= 50 kA/1 s
Supply units with the ABB-defined main breaker and fuses:
Rated peak withstand current I
pk
= 143 kA
Rated short-time withstand current I
cw
= 65 kA/1 s
Short-circuit current
protection (UL 508A)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with T class fuses.
Short-circuit current
protection
(CSA C22.2 No. 14-13)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with T class fuses.
Power factor Fundamental power factor = 0.98 (at nominal load)
Overvoltage category OVCIII (altitude 4000 m)
Motor types Asynchronous AC induction motors, permanent magnet synchronous motors and
AC induction servomotors, ABB synchronous reluctance (SynRM) motors
Voltage (U
2
) 0 to U
1
, 3-phase symmetrical, U
max
at the field weakening point
Frequency (f
2
) 0…500 Hz
For higher operational output frequencies, contact your local ABB
representative.
Operation above 150 Hz may require type-specific derating. For more
information, contact your local ABB representative.
Current See the rating tables.
Switching frequency 3 kHz (typical). The switching frequency can vary per frame and voltage. For
exact values, contact your local ABB representative.
Maximum recommended
motor cable length
500 m (1640 ft).
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and
characteristics. Contact ABB for more information. Note that a sine filter
(optional) at the drive output also causes a voltage decrease.
Note: With motor cables longer than 150 m (492 ft) the EMC Directive
requirements may not be fulfilled.