354 The Safe torque off function
Single inverter unit (internal power supply)
Dual-channel connection
Single-channel connection
+24 V
OUT1
SGND
IN2
U2, V2, W2
Control logic
UDC+
UDC–
Inverter unit
Control unit
A
K
IN1
+24 V
OUT1
SGND
IN2
K
IN1
Inverter unit
Control unit
Notes:
Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL
classification is given.
Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded
cable. For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.