EasyManuals Logo

ABB ControlMaster CM10 User Manual

ABB ControlMaster CM10
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/8,
1
/4 and
1
/2 DIN 7 Advanced Level
IM/CM/S–EN Rev. R 43
7.3 Input/Output
Enables analog and digital inputs / outputs and relays to be configured.
Analog Inputs
Analog Input 1 (4)*
Input Type Input types comprise:
Millivolts, Milliamps, Volts, Resistance (Ohms), RTD, Thermocouple, Digital
volt-free, 24V Digital, Freq. Input, Pulse Input
.
Additional Input Type comments:
Digital Volt Free
Acts as a digital input.
Freq. Input
Sets the maximum frequency and equivalent flow rate in the engineering range 0 to 6 KHz.
(A frequency of 0.01 to 6 KHz can be used to create an analog value.)
Pulse Input
This parameter counts pulses and is recommended only for use with electromagnetic
flowmeters.
*Analog Inputs 2 to 4: Freq Input, Pulse Input and Resistance not available. A Thermocouple input type can be set only if the first input is set to
Thermocouple.
Menu
Input/Output

Table of Contents

Other manuals for ABB ControlMaster CM10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ControlMaster CM10 and is the answer not in the manual?

ABB ControlMaster CM10 Specifications

General IconGeneral
BrandABB
ModelControlMaster CM10
CategoryController
LanguageEnglish

Related product manuals