ControlMaster CM15 and CMF160
Universal process indicator
1
/8 DIN 7 Advanced Level
IM/CM/I–EN Rev. P 45
… Input/Output / …Analog Input 1 (4)
Elect. Low Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Ohms.
Linear Inputs Standard Analog Input Accuracy (% of
Reading)
Millivolts 0 to 150 mV 0.1 % or ±20 µV
Milliamps 0 to 45 mA 0.2 % or ±10 µA
Volts 0 to 25 V 0.2 % or ±20 mV
Resistance (low) 0 to 550 0.2 % or ±1
Resistance (high) 0 to 10 k 0.1 % or ±5
Elect. High Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Freq. Input.
Linearizer Selects the linearizer type required to condition the input signal.
Notes. For thermocouple applications using an external fixed cold junction, set Input
Type to Millivolts (see page 44) and select the appropriate linearizer type.
Not applicable for Pulse Input, Digital volt-free, 24V Digital parameters – see page 44.