ControlMaster CM15 and CMF160
Universal process indicator
1
/8 DIN 7 Advanced Level
46 IM/CM/I–EN Rev. P
… Input/Output / …Analog Input 1 (4)
Eng Units The selected units are used by the linearizer and displayed in the Operator pages.
Not applicable for: Pulse Input, Digital volt-free and 24V Digital parameters.
Thermocouple and RTD inputs (see page 44) are restricted to deg C, deg F, Kelvin
see Appendix C, page 99 for analog input (engineering) units.
Eng. Dps Engineering decimal places – selects the resolution required to be displayed for the input
value.
Eng. Low
Eng High
Specifies the engineering low (minimum) / high (maximum) value.
For example, for an electrical input range of 4.0 to 20.0 mA, representing a pressure
range of 50 to 250 bar, set the Eng Low value to 50.0 and the Eng High value to 250.0.
Not applicable for Pulse Input – see page 44.
Pulse Units Selects the unit of measure for the pulse input type.
Pulse / Unit Sets the number of pulses required to represent 1 pulse unit (as set above).
For example, if Pulse Units = Kl and Pulse / Unit = 10.00000000, each pulse represents
0.1 Kl, 10 pulses = 1 Kl.