132
3ADW000462R0401 DCS880 Hardware manual e d
Voltage ripple of voltage U
DC
depending on operation modes.
DCSLink communication
The field converter is controlled from armature converter via DCSLink based on CAN hardware.
Node address is set by:
S800 digit 0 (node address 00 is not possible!).
S801 digit 10.
Same node address must be selected in the corresponding armature converter.
Example: Node address = 13 ==> S800 = 3 and S801 = 1.
The communication speed is set by S1100.
S1100:6 S1100:5 S1100:4 Baudrate
[kBaud]
Selection in armature converter,
parameter (94.02)
OFF OFF OFF 20 0
OFF OFF ON 50 1
OFF ON OFF 125 2
OFF ON ON 250 3
ON OFF OFF 500 4
ON OFF ON 800 5
ON ON OFF 888 6
ON ON ON 1000 7
DZ_LIN_014_Spg-well_a.ai
Voltage ripple Vsec
U
DC
Field
Single-phase, half-controlled
3-phase, half-controlled
3-phase, full-controlled
1
0.75
0.5
0.25
0
0.1 0.4 0.7 1
X1:1
2
SF_FEX4_002_DCSLink_a.dsf
X3:1
2
3
24 V / 200 mA
S1100:1
CANL
CANH
S1100:3
GNDB
S1100:2
SDCS-FEX-4
Termination 200 kOhm
Incoming power Remarks
24 V 200 mA 24 V grounded via X51 of SDCS-DSL-H1x
DSL communication Remarks
Bus termination
S1100: 1 = ON 120 Ohm
1 = OFF No termination
Ground termination
S1100: 2 = ON 200 kOhm R-C ground termination
3 = ON 0 Ohm ground termination
2, 3 = OFF No termination
S800
S801